diesel Fuel incinerators | HICLOVER|Clover Incinerator

diesel Fuel incinerators

16.  The supplier must provide necessary information for the best of the installation.  This incinerator with “PYROLYTIC” 

combustion must have:

17.  A combustion chamber of waste:

  Perfectly tight door for the manual loading of waste.  The loading should be manual, batch load.

  A burner of lighting which the use is limited to the ignition of waste.

  Frontage of loading with door seals gone up on hinges, wheel of screw plug, flexible joint, and stuffing insulating out 

of refractory.

  The insulation of the combustion chamber should be composed of refractory bricks, having a high content of aluminium and 

insulates bricks in order to assure a minimum temperature on the outside sheet metal.

  Composition of the refractory;

  Refractory concrete:

    Thickness :>100mm

    Nature: 42% of Al203

  Insulate in fibrous panels:

    Thickness: >75mm

  Nature: Calcium silicate.

  Burner of lighting of waste, with fuel, standard mono-bloc casting guiding plunging flame, lighting and safety of 

electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.

  Plate of combustion in Carborundum, avoiding the fixing of glass and slags.

18.  A chamber of post combustion of gases

  A burner of combustion of gases,

  A device of injection of air allowing a total re-combustion of gases,

  A device of air inlet of cooling of waste gases,

  A sheath of evacuation of the gases burnt,

  Carcass in strong sheet steel with support of connection

  Composition of the refractory;

  Refractory concrete:

    Thickness :>150mm

    Nature: 65%% of Al203

  Insulate in fibrous panels:

    Thickness: >85mm

    Nature: Calcium

  Burner with fuel, mono-bloc casting guiding type with horizontal flame, lighting and safety of electronic ignition, 

permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.

  A secondary injection of air to ensure perfect oxygen content.